Overload Relays are used to protect Electric Motor from failure due to high current drawn by motor.Electric motor has 33% of it's cost in total Air Compressor unit,so it is our duty to protect Electric Motor from any type of failure.Overload Relays are the only solutation to protect motor from high current.Overload Relays are generally of two types one is "Electro-magnetic" and another is "Thermal".

I have already given details about Thermal Overload Relay in past.In this post,you will find details about "Electro-magnetic Overload Relay" which is
somewhat outdated now a days,but still some old Air Compressor units are having these type of Relays.

The Electro-magnetic Overload Relays consist of a coil or solenoid carrying the line current (or a portion of it through current transformers) with an armature
which when attracted sufficiently operates the release circuit or latch.A time lag feature is in corporated to guard against unnecessary operation from
temporary Overloads due to the normal operation of the machines which are being driven.Time lag is obtained by means of Dash pot (otherwise the action would be practically instantaneous) fitted to the Oil Circuit Breaker (OCB) controlling the stator circuits.

Construction and Adjustment of Dash pot.

The time lag consist of BODY CASTING,MOVEABLE PLUNGER,OIL RETAINING SCREW CUP.The moveable plunger comprises the core of the Overload release,to which is fitted a specially shaped brass disc moving in a restriction in the body casting,by turning the screw cap the position of the disc within the restriction is varied.

The time lag are despatched dry and must filled with special time lag oil (SAE-60 grade) provided in seperate containers in the Circuit Breaker.While fitting
remove screw "A".It is not necessary to remove the bottom cup "B" and on no account should screw "C" be removed.Adjustment of the Overload setting is
made by slackening screw "D" and sliding the body casting up or down,until the top face coincides with the calibration marking required on the calibration
tube,screw "D' is then tightened.The bottom rotatable cup "B" is now described reset themselves after operation within few second.

This type of Overload Relays are very simple in operation but due care must taken for accurate operation.All the marks "A","B","C"&"D" are embossed on
respective spaces,you have to indentify first before working on "Electro-magnetic Overload Relay".




For more details, visit http://www.pnengineering.blogspot.com/




Responses


No responses found. Be the first to respond and make money from revenue sharing program.

Feedbacks      
Popular Tags   What are tags ?   Search Tags  
(No tags found.)

Post Feedback


This is a strictly moderated forum. Only approved messages will appear in the site. Please use 'Spell Check' in Google toolbar before you submit.
You must Sign In to post a response.
Next Resource: Important Mass Communication Entrance Examinations
Previous Resource: Ayurvedic Colleges in Kerala
Return to Discussion Resource Index
Post New Resource
Category: Education


Post resources and earn money!
 
Related Resources


Contact Us    Privacy Policy    Terms Of Use   

SpiderWorks Technologies Pvt Ltd. 2006 - 2007 All Rights Reserved.